CVEfocus › CVE database › CVE-2012-6436

CVE-2012-6436Rockwell Automation ControlLogix PLC Improper Input Validation

CVSS 7.5 HighEPSS 35.2% (higher than 98% of CVEs)Published 2013-01-24Updated 2026-06-03Assigner: icscert

The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the CPU to crash. Successful exploitation of this vulnerability could cause loss of availability and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400

CWE-119

What to do

Likely to be exploited: EPSS gives a 35% chance of exploitation in the next 30 days. Treat it as urgent if you run an affected version.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: According to Rockwell, any of the above products that become affected by a vulnerability can be reset by rebooting or power cycling the affected product. After the reboot, the affected product may require some reconfiguration. To mitigate the vulnerabilities, Rockwell has developed and released security patches on July 18, 2012, to address each of the issues. To download and install the patches please refer to Rockwell’s Advisories at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156 For more information on security with Rockwell Automation products, please refer to Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102 .

Workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products. To mitigate the vulnerabilities pertaining to receiving valid CIP packets: * Block all traffic to the Ethernet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by restricting or blocking access to TCP and UDP Ports 2222 and 44818 using appropriate security technology such as a firewall or Unified Threat Management (UTM). * Employ a UTM appliance that specifically supports CIP message filtering. In addition to the above, Rockwell recommends concerned customers remain vigilant and continue to follow security strategies that help reduce risk and enhance overall control system security. Where possible, they suggest you apply multiple…

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.