CVE-2012-6437Rockwell Automation ControlLogix PLC Improper Authentication
The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause loss of availability, integrity, and confidentiality and a disruption in communications with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400
What to do
Likely to be exploited: EPSS gives a 11% chance of exploitation in the next 30 days. Treat it as urgent if you run an affected version.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules: affected: All
- Rockwell Automation CompactLogix L32E and L35E controllers: affected: All
- Rockwell Automation 1788-ENBT FLEXLogix adapter: affected: All
- Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter: affected: All
- Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix: affected: up to 18
- Rockwell Automation CompactLogix and SoftLogix controllers: affected: up to 19
- Rockwell Automation ControlLogix and GuardLogix controllers: affected: up to 20
- Rockwell Automation MicroLogix: affected: 1100, 1400
Solution: According to Rockwell, any of the above products that become affected by a vulnerability can be reset by rebooting or power cycling the affected product. After the reboot, the affected product may require some reconfiguration. To mitigate the vulnerabilities, Rockwell has developed and released security patches on July 18, 2012, to address each of the issues. To download and install the patches please refer to Rockwell’s Advisories at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155 https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156 For more information on security with Rockwell Automation products, please refer to Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102 .
Workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products. To mitigate the vulnerability with the Web server password authentication mechanism: * Upgrade the MicroLogix 1400 firmware to FRN 12 or higher. * Because of limitations in the MicroLogix 1100 platform, none of the firmware updates will be able to fix this issue, so users should use the following techniques to help reduce the likelihood of compromise. * Where possible, disable the Web server and change all default Administrator and Guest passwords. * If Web server functionality is needed, then Rockwell recommends upgrading the product’s firmware to the most current version to have the newest enhanced protections available such as: * When a controller receives…
References
- https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03
- https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154
- https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155
- https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156
- http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.