CVE-2014-5410Rockwell Automation Micrologix 1400 Improper Input Validation
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Rockwell Automation Allen-Bradley MicroLogix 1400: affected: up to 1766-Lxxxxx Series A FRN 7, up to 1766-Lxxxxx Series B FRN 15.000, Series B FRN 15.001 or higher not affected
Solution: Rockwell Automation has released a new version of MicroLogix 1400 Series B firmware to address the vulnerability and reduce associated risk to successful exploitation. Subsequent versions of MicroLogix 1400 Series B firmware and newer will incorporate these same enhancements. Rockwell Automation recommends the following immediate mitigation strategies (when possible, multiple strategies should be employed simultaneously): * Upgrade all MicroLogix 1400 Series B controllers to Series B FRN 15.001 or higher. Current firmware for the MicroLogix 1400 Series B platform can be obtained at the following web address: http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page Please refer to Rockwell Automation’s product disclosure (AID 620295) for more information on this topic available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295
Workaround: Users with Series A and Series B controllers are also recommended to apply the following risk mitigations: * Do not enable DNP3 communication in the product unless required. * Where appropriate, prohibit DNP3 communication that originates outside the perimeter of the manufacturing zone from entry into the zone by blocking communication directed at Ethernet communication Port 20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a firewall, UTM devices, or other security appliance) *Note: Ports 20000/TCP and 20000/UDP are factory defaults as per the DNP3 specification but can be reconfigured by the product owner. * Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked. * Restrict physical and electronic…
References
- https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295
- https://www.cisa.gov/news-events/ics-advisories/icsa-14-254-02
- https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2014/icsa-14-254-02.json
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.