CVE-2018-11452
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the EN100 communication module if oscillographs are running. A manual restart is required to recover the EN100 module functionality. Successful exploitation requires an attacker with network access to send multiple packets to the EN100 module. As a precondition the IEC 61850-MMS communication needs to be activated on the affected EN100 modules. No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by siemens, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module: affected: All versions < V4.33
- Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module: affected: All versions
- Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module: affected: All versions
- Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module: affected: All versions
- Siemens AG Firmware variant IEC104 for EN100 Ethernet module: affected: All versions < V1.22
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-635129.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-325546.pdf
- https://www.securityfocus.com/bid/106221
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.