CVEfocus › CVE database › CVE-2019-10953

CVE-2019-10953

CVSS 7.5 HighEPSS 3.5% (higher than 90% of CVEs)Published 2019-04-17Updated 2026-06-04Assigner: icscert

ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.

CWE-400

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: Fixes are available in Schneider Electric Modicon M221 firmware v1.10.0.0 and EcoStruxure Machine Expert – Basic v1.0 software (formerly SoMachine Basic) using either of the following options: Use this link to download the Machine Expert Basic software. Or run the Schneider Electric Software Update tool in order to download and install EcoStruxure Machine Expert – Basic v1.0 software. For additional information, see the Schneider Electric security notice SEVD-2019-045-01. (https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2019-045-01) Schneider Electric strongly recommends following industry cybersecurity best practices, such as: * Physical controls should be in place so no unauthorized person would have access to the ICS and safety controllers, peripheral equipment, or the ICS and safety networks. * All controllers should reside in locked cabinets and never be left in the…

Workaround: ABB concludes the reported behavior is not a vulnerability but is due to a misconfiguration of the PLC watchdog, which was left in the default factory settings. This has led to a configuration that does not match the expectations expressed in the test cases and the result is the PLC not reacting as intended. This misconfiguration can be fixed by setting an appropriate combination of task priority, task cycle time, and watchdog settings. Please see the “Onboard Ethernet Handling in CPU Firmware” chapter (System Technology for AC500 V2 Products > System Technology of CPU and Overall System > Onboard Technologies > Ethernet > Ethernet Protocols and Ports for AC500 V2 Products > Onboard Ethernet Handling in CPU Firmware) for further guidance.

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.