CVE-2019-10954Rockwell Automation CompactLogix 5370 Stack-based Buffer Overflow
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Rockwell Automation CompactLogix 5370 L1 controllers: affected: before 20 - 30
- Rockwell Automation CompactLogix 5370 L2 controllers: affected: before 20 - 30
- Rockwell Automation CompactLogix 5370 L3 controllers: affected: before 20 - 30
- Rockwell Automation Compact GuardLogix 5370 controllers: affected: before 20 - 30
- Rockwell Automation Armor Compact GuardLogix 5370 controllers: affected: before 20 - 30
Solution: Rockwell recommends the following: * Rockwell Automation strongly encourages users to apply the latest available version of firmware to keep up to date with the latest features, anomaly fixes, and security improvements. Update to a version of firmware as listed below that mitigates the associated risk: * Apply FRN 31.011 or later from: https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?Keyword=5370&crumb=112 https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx * For EtherNet/IP-based vulnerabilities (ID 1-14), block all traffic to and from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP/UDP and Port 44818/TCP/UDP using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see…
References
- https://ics-cert.us-cert.gov/advisories/ICSA-19-120-01
- http://www.securityfocus.com/bid/108118
- https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1075979
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.