CVEfocus › CVE database › CVE-2020-25178

CVE-2020-25178Rockwell Automation ISaGRAF5 Runtime Cleartext Transmission of Sensitive Information

CVSS 7.5 HighEPSS 1.7% (higher than 77% of CVEs)Published 2022-03-18Updated 2025-04-16Assigner: icscert

ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.

CWE-319

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other…

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.