CVEfocus › CVE database › CVE-2020-25180

CVE-2020-25180Rockwell Automation ISaGRAF5 Runtime Use of Hard-coded Cryptographic Key

CVSS 5.3 MediumEPSS 1.2% (higher than 67% of CVEs)Published 2022-03-18Updated 2025-04-16Assigner: icscert

Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.

CWE-321

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other…

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.