CVEfocus › CVE database › CVE-2021-35533

CVE-2021-35533Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

CVSS 7.5 HighEPSS 0.9% (higher than 60% of CVEs)Published 2021-11-26Updated 2024-09-16Assigner: Hitachi Energy

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

CWE-20

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by Hitachi Energy, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: - Disable BCI IEC 60870-5-104 function by configuration if it is not used. - Update to RTU500 series CMU Firmware version 12.6.5.0 or later (e.g., RTU500 CMU Firmware version 12.7.* or CMU Firmware version 13.2.* or later).

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.