CVE-2021-44477GE Gas Power ToolBoxST Improper Restriction of XML External Entity Reference
GE Gas Power ToolBoxST Version v04.07.05C suffers from an XML external entity (XXE) vulnerability using the DTD parameter entities technique that could result in disclosure and retrieval of arbitrary data on the affected node via an out-of-band (OOB) attack. The vulnerability is triggered when input passed to the XML parser is not sanitized while parsing the XML project/template file.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- GE Gas Power ToolBoxST: affected: unspecified to before 07.09.07C; fixed in
07.09.07C
Solution: GE addressed CVE-2021-44477 in ToolBoxST OS Version 07.09.07C and above by disabling the use of DTD’s, which are not necessary for ToolBoxST functionality. GE upgraded the Ionic library in ToolBoxST Version 7.8.0 to resolve CVE-2018-16202 Users should ensure they follow the password protection and network segmentation guidance laid out in GEH-6839 Secure Deployment Guide. Additionally, the use of SDI Secure Mode offers considerable protection against this attack as the threat actor must be able to perform a download to the controller over SDI. Secure Mode validates authenticity and protects against spoofing of SDI commands.
Workaround: GE Gas Power Cybersecurity and Engineering teams will continue to investigate internally as well as monitor industry-based news for any changes or updates. To reduce the risk vulnerabilities such as these may represent to the controls network, GE recommends the implementation of a good defense-in-depth strategy as detailed in GEH-6839. Some recommended controls include: Minimize network exposure for all controllers with the use of network segmentation, placement of controllers behind controls network firewalls and ensure they are not accessible from the Internet. Block suspicious external IP addresses at the controls network firewalls. Monitor traffic internally for unusual behavior. When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also…
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.