CVEfocus › CVE database › CVE-2022-2004

CVE-2022-2004AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption

CVSS 7.5 HighEPSS 1.1% (higher than 65% of CVEs)Published 2022-08-31Updated 2025-04-16Assigner: icscert

AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;

CWE-400

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002. Additional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts. Please see the security network practices below for CVE-2022-2004. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.…

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.