CVE-2022-2485AutomationDirect Stride Field I/O Cleartext Transmission of Sensitive Information
Any attempt (good or bad) to log into AutomationDirect Stride Field I/O with a web browser may result in the device responding with its password in the communication packets.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- AutomationDirect SIO-MB04RTDS: affected: unspecified to before 8.3.4.0; fixed in
8.3.4.0 - AutomationDirect SIO- MB04ADS: affected: unspecified to before 8.4.3.0; fixed in
8.4.3.0 - AutomationDirect SIO-MB04THMS: affected: unspecified to before 8.5.4.0; fixed in
8.5.4.0 - AutomationDirect SIO-MB08ADS-1: affected: unspecified to before 8.6.3.0; fixed in
8.6.3.0 - AutomationDirect SIO-MB08ADS-2: affected: unspecified to before 8.7.3.0; fixed in
8.7.3.0 - AutomationDirect SIO-MB08THMS: affected: unspecified to before 8.8.4.0; fixed in
8.8.4.0 - AutomationDirect SIO-MB04DAS: affected: unspecified to before 8.11.3.0; fixed in
8.11.3.0 - AutomationDirect SIO-MB12CDR: affected: unspecified to before 8.0.4.0; fixed in
8.0.4.0 - AutomationDirect SIO-MB16CDD2: affected: unspecified to before 8.1.4.0; fixed in
8.1.4.0 - AutomationDirect SIO-MB16ND3: affected: unspecified to before 8.2.4.00; fixed in
8.2.4.00 - AutomationDirect SIO-MB12CDR: affected: batch number (B/N) 5714442222
- AutomationDirect SIO-MB04ADS: affected: B/N 5714442222
Solution: AutomationDirect recommends users upgrade the Stride Modbus Field I/O units listed in the affected products section with the firmware associated with the part number. Firmware can be downloaded from the AutomationDirect software downloads page. The modules with a listed B/N number in the affected products section have a firmware update issue and must be returned to AutomationDirect for replacement modules; users can create an RMA on the AutomationDirect website. Automation networks and systems may have built-in password protection schemes, but this is only one step in securing systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products and SCADA systems perform their own network security analysis to determine the proper level of…
Workaround: AutomationDirect has identified the specific mitigation actions listed below: Secure physical access. Isolate and air gap networks when possible. Follow the security considerations in the Automation Direct Security Considerations document. https://support.automationdirect.com/docs/securityconsiderations.pdf
References
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-202-05
- https://cdn.automationdirect.com/static/firmware/product_advisory/PA-COM-006.pdf
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.