CVE-2022-2513Cleartext Credentials Vulnerability on Hitachi Energy’s Multiple IED Connectivity…
A vulnerability exists in the Intelligent Electronic Device (IED) Connectivity Package (ConnPack) credential storage function in Hitachi Energy’s PCM600 product included in the versions listed below, where IEDs credentials are stored in a cleartext format in the PCM600 database and logs files. An attacker having get access to the exported backup file can exploit the vulnerability and obtain user credentials of the IEDs. Additionally, an attacker with administrator access to the PCM600 host machine can obtain other user credentials by analyzing database log files. The credentials may be used to perform unauthorized modifications such as loading incorrect configurations, reboot the IEDs or cause a denial-of-service on the IEDs.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by Hitachi Energy, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Hitachi Energy PCM600: affected: v2.6 to 2.11 Hotfix 20220617
- Hitachi Energy 670 Connectivity Package: affected: 3.0 to 3.4.1
- Hitachi Energy 650 Connectivity Package: affected: 1.3 to 2.4.1
- Hitachi Energy SAM600-IO Connectivity Package: affected: 1.0 to 1.2
- Hitachi Energy GMS600 Connectivity Package: affected: 1.3 to 1.3.1
- Hitachi Energy PWC600 Connectivity Package: affected: 1.1 to 1.3
Solution: Update to PCM600 v2.11 Hotfix 20240426 or apply mitigation factors/workarounds as described in the Mitigation Factors/Workarounds Section. List of CPEs: cpe:2.3:a:hitachienergy:pcm600:*:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.4.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.2.6:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.1.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:670ConnectivityPackage:3.0.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.4.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.3.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.2.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:2.1.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:650ConnectivityPackage:1.3.0:*:*:*:*:*:*:*…
Workaround: It is recommended to implement and continuously revise least privileges principles to minimize permissions and accesses to PCM600 related resources, included the backup file, PCMI/PCMP file. Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to…
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.