CVE-2022-4608
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by Hitachi Energy, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Hitachi Energy RTU500 series: affected: RTU500 series CMU Firmware version 13.3.1, RTU500 series CMU Firmware version 13.3.2, RTU500 series CMU Firmware version 13.3.3 not affected, RTU500 series CMU Firmware version 13.4.1 not affected
Solution: Update to CMU Firmware versions 13.3.3 or 13.4.1.
Workaround: Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.
Vendor advisories:
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&Documen… (vendor-advisory)
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.