CVE-2023-2262Rockwell Automation Select Logix Communication Modules Vulnerable to Email Object Buffer…
A buffer overflow vulnerability exists in the Rockwell Automation select 1756-EN* communication devices. If exploited, a threat actor could potentially leverage this vulnerability to perform a remote code execution. To exploit this vulnerability, a threat actor would have to send a maliciously crafted CIP request to device.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by Rockwell, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Rockwell Automation 1756-EN2T Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2T Series D: affected: <=11.002
- Rockwell Automation 1756-EN2TK Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TXT Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TXT Series D: affected: <=11.002
- Rockwell Automation 1756-EN2TP Series A: affected: <=11.002
- Rockwell Automation 1756-EN2TPK Series A: affected: <=11.002
- Rockwell Auotmation 1756-EN2TPXT Series A: affected: <=11.002
- Rockwell Automation 1756-EN2TR Series A, B: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TR Series C: affected: <=11.002
- Rockwell Automation 1756-EN2TRK Series A, B: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TRK Series C: affected: <=11.002
Solution: Update firmware. Update EN2* ControlLogix communications modules to mitigated firmware. * Restrict traffic to the SMTP port (25), if not needed. * Customers using the EN2/EN3 versions 10.x and higher can disable the email object, if not needed. Instructions can be found in the EtherNet/IP Network Devices User Manual (rockwellautomation.com) https://literature.rockwellautomation.com/idc/groups/literature/documents/um/enet-um006_-en-p.pdf , publication ENET-UM006. * QA43240 - Recommended Security Guidelines from Rockwell Automation https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.