CVE-2023-3595Rockwell Automation ControlLogix Communication Modules Vulnerable to Remote Code Execution
Where this vulnerability exists in the Rockwell Automation 1756 EN2* and 1756 EN3* ControlLogix communication products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by Rockwell, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Rockwell Automation 1756-EN2T Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2T Series D: affected: <=11.003
- Rockwell Automation 1756-EN2TK Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TXT Series A, B, C: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TXT Series D: affected: <=11.003
- Rockwell Automation 1756-EN2TP Series A: affected: <=11.003
- Rockwell Automation 1756-EN2TPK Series A: affected: <=11.003
- Rockwell Auotmation 1756-EN2TPXT Series A: affected: <=11.003
- Rockwell Automation 1756-EN2TR Series A, B: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TR Series C: affected: <=11.003
- Rockwell Automation 1756-EN2TRK Series A, B: affected: <=5.008 & 5.028
- Rockwell Automation 1756-EN2TRK Series C: affected: <=11.003
Solution: * Update firmware. Update EN2* ControlLogix communications modules to mitigated firmware. * Properly segment networks. Given a cyber actor would require network connectivity to the communication module to exploit the vulnerability, organizations should ensure ICS/SCADA networks are properly segmented within the process structure as well as from the Internet and other non-essential networks. * Implement detection signatures. Use appended Snort signatures to monitor and detect anomalous Common Industrial Protocol (CIP) packets to Rockwell Automation devices.
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.