CVE-2024-10490Authentication bypass flaw in several mapp components
An “Authentication Bypass Using an Alternate Path or Channel” vulnerability in the OPC UA Server configuration required for B&R mapp Cockpit before 6.0, B&R mapp View before 6.0, B&R mapp Services before 6.0, B&R mapp Motion before 6.0 and B&R mapp Vision before 6.0 may be used by an unauthenticated network-based attacker to cause information disclosure, unintended change of data, or denial of service conditions. B&R mapp Services is only affected, when mpUserX or mpCodeBox are used in the Automation Studio project.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by ABB, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- B&R Industrial Automation GmbH B&R mapp Cockpit: affected: 5.0;0 to before 6.0;0
- B&R Industrial Automation GmbH B&R mapp View: affected: 5.0 to before 6.0; fixed in
6.0 - B&R Industrial Automation GmbH B&R mapp Services: affected: 5.0 to before 6.0; fixed in
6.0 - B&R Industrial Automation GmbH B&R mapp Motion: affected: 5.0 to before 6.0; fixed in
6.0 - B&R Industrial Automation GmbH B&R mapp Vision: affected: 5.0 to before 6.0; fixed in
6.0
Workaround: Enforce client device authentication in the configuration of the OPC UA server. Configure a proper “SecurityPolicy” for OPC UA Server ( Automation Help https://help.br-automation.com/#/en/4/communication/opcua/runtime/opcua_config_security.html ) and select a “CertificateStore configuration” which has “Validate SSL communication partner” set to “on” ( Automation Help https://help.br-automation.com/#/en/4/access_and_security%2Fssl%2Fssl_configuration.html ). Limit access to the OPC UA Server (default 4840/tcp) to IP addresses or IP subnets which are running instances of impacted mapp components and legitime OPC UA clients using the B&R Automation Runtime host-based firewall. Ensure only trusted personal is able to access devices with the specified IP (range) and enforce strict authentication on these devices. Please be aware that B&R Automation Runtime and its services (like mapp…
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.