CVE-2025-0960AutomationDirect C-more EA9 HMI Classic Buffer Overflow
AutomationDirect C-more EA9 HMI contains a function with bounds checks that can be skipped, which could result in an attacker abusing the function to cause a denial-of-service condition or achieving remote code execution on the affected device.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- AutomationDirect C-more EA9 HMI EA9-T6CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T7CL-R: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T7CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T8CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T10CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T10WCL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T12CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T15CL-R: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-T15CL: affected: up to v6.79
- AutomationDirect C-more EA9 HMI EA9-RHMI: affected: up to v6.79
Solution: AutomationDirect recommends that users update C-MORE EA9 HMI software and firmware to V6.80 https://support.automationdirect.com/firmware/historydetail.php .
Workaround: If an immediate update is not feasible, AutomationDirect recommends considering the following interim steps until the programming software can be updated: * Isolate the HMI Workstation: Disconnect the HMI from external networks (e.g., internet or corporate LAN) to limit exposure to external threats. * Use dedicated, secure internal networks or air-gapped systems for communication with programmable devices. * Control Access: Restrict physical and logical access to the HMI to authorized personnel only. * Implement Whitelisting: Use application whitelisting to allow only pre-approved and trusted software to execute on the HMI. Block untrusted or unauthorized applications. * Apply Endpoint Security Measures: Use antivirus or endpoint detection and response (EDR) tools to monitor for and mitigate threats. Ensure that host-based firewalls are properly configured to block unauthorized access.…
References
- https://www.cisa.gov/news-events/ics-advisories/icsa-25-035-08
- https://community.automationdirect.com/s/cybersecurity/security-advisories
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.