CVEfocus › CVE database › CVE-2025-58456

CVE-2025-58456AutomationDirect Productivity Suite Relative Path Traversal

CVSS 6.8 MediumEPSS 0.9% (higher than 58% of CVEs)Published 2025-10-23Updated 2025-10-24Assigner: icscert

A relative path traversal vulnerability was discovered in Productivity Suite software version 4.4.1.19. The vulnerability allows an unauthenticated remote attacker to interact with the ProductivityService PLC simulator and read arbitrary files on the target machine.

CWE-23

What to do

None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.

Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.

curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \
  -H "Content-Type: text/plain" --data-binary @inventory.txt

What the vendor says

As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.

Solution: AutomationDirect recommends that users do the following: * Update the Productivity Suite programming software to version 4.5.0.x or higher. * Update the firmware of Productivity PLCs to the latest version. https://www.automationdirect.com/support/software-downloads * Although automation networks and systems come equipped with built-in password protection mechanisms, this represents a fraction of the security measures needed to safeguard these systems. * It is imperative that automation control system networks integrate data protection and security measures that match, if not exceed, the robustness of conventional business computer systems. * AutomationDirect advises users of PLCs, HMI products, and SCADA systems to conduct a thorough network security analysis to ascertain the appropriate level of security necessary for their specific application.

Workaround: AutomationDirect has identified the following mitigations for instances where systems cannot be upgraded to the latest version: * Physically disconnect the PLC from any external networks, including the internet, local area networks (LANs), and other interconnected systems. * Configure network segmentation to isolate the PLC from other devices and systems within the organization. * Implement firewall rules or network access control (NAC) policies to block incoming and outgoing traffic to the PLC. * Please refer to AutomationDirect's security considerations https://support.automationdirect.com/docs/securityconsiderations.pdf for additional information. * If you have any questions regarding this issue, please contact AutomationDirect Technical Support at 770-844-4200 or 800-633-0405 for further assistance.

References

About this page

Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.