CVE-2026-124759Alarm frames are accepted from any source address
P-Net before 1.0.4 routes a received RTA alarm frame to an Application Relationship using only the destination alarm reference in the frame, without checking the source of the frame. A host with ADJACENT network access can abort an established Application Relationship with a single alarm ERROR frame, or deliver forged alarm notifications with chosen type, slot, subslot, USI and payload to the application.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by rt-labs, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- RT-Labs P-Net: affected: before 1.0.4, 1.0.4 and later; fixed in
1.0.4
Solution: Upgrade to P-Net 1.0.4 or later, which ignores alarm frames that do not come from the IO-controller of the Application Relationship. It reduces the risk but does not remove it, see Remaining Risk.
Workaround: Isolate the network of the device from untrusted hosts, for example by a firewall or a separate network,. The remaining risk is that a host on the network that knows the MAC address of the IO-controller and the alarm references can still send forged alarm frames.
References
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.