CVE-2026-4293Kieback & Peter DDC Building Controllers Cross-site Scripting
The affected Kieback & Peter DDC building controllers are vulnerable to cross-site scripting, enabling JavaScript to be executed by the victim's browser, which allows the attacker to control the browser.
What to do
None of the Linux distributions or Windows releases we track list an affected package for this CVE. Check the vendor-reported products below.
Is your server affected? One read-only command checks every installed package against this CVE and all others, using each vendor's fixed versions. Get started or get a free API key.
curl -sS "https://api.cvefocus.com/v1/check?format=text" -H "Authorization: Bearer $CVEFOCUS_KEY" \ -H "Content-Type: text/plain" --data-binary @inventory.txt
What the vendor says
As published in the CVE record by icscert, the CVE's assigner (usually the vendor). Check the vendor's advisory before acting.
- Kieback & Peter DDC4002: affected: up to 1.12.14
- Kieback & Peter DDC4100: affected: up to 1.12.14
- Kieback & Peter DDC4200: affected: up to 1.12.14
- Kieback & Peter DDC4200-L: affected: up to 1.12.14
- Kieback & Peter DDC4400: affected: up to 1.12.14
- Kieback & Peter DDC4002e: affected: up to 1.23.4
- Kieback & Peter DDC4200e: affected: up to 1.23.4
- Kieback & Peter DDC4400e: affected: up to 1.23.4
- Kieback & Peter DDC4020e: affected: up to 1.23.4
- Kieback & Peter DDC4040e: affected: up to 1.23.4
- Kieback & Peter DDC520: affected: up to 1.24.1
Solution: For DDC520, DDC4002e, DDC4200e, DDC4400e, DDC4020e, and DDC4040e controllers, update the firmware to the latest available version: * DDC4002e: Update to version 1.23.5 or newer * DDC4200e: Update to version 1.23.5 or newer * DDC4400e: Update to version 1.23.5 or newer * DDC4020e: Update to version 1.23.5 or newer * DDC4040e: Update to version 1.23.5 or newer * DDC520: Update to version 1.24.2 or newer
Workaround: Kieback & Peter DDC Building Controllers are developed and designed for use in closed building automation networks. The system is protected by a multi-level perimeter against attacks, especially from outside, by dividing it into operational technology (OT) zones with firewalls. Building automation systems (BA systems) in general should not be directly accessible from untrusted networks, especially from the Internet, but should be protected by consistently applying the defense-in-depth strategy. This concept is supported by organizational measures in the building as part of a safety management system. In order to achieve safety, measures are required at all levels.
References
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-139-05
- https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-139-05.json
About this page
Compiled by CVEfocus from the CVE List, the security data and VEX statements of Ubuntu, Debian, Red Hat, AlmaLinux, Rocky Linux and Microsoft, CISA's Known Exploited Vulnerabilities catalog and FIRST EPSS, refreshed several times a day (data status). Information only; see the disclaimer. Official record: cve.org · NVD.